Cross sectional area mm² | Minimum average thickness of insulation mm | Nominal thickness of PVC/LSOH bedding mm | Nominal number and diameter of armoured wires no/mm | Nominal thickness of PVC/LSOH oversheath mm | Approx. overall diameter of cable mm |
70 | 3.4 | 1.4 | 2.5 | 2.7 | 54.5 |
95 | 3.4 | 1.5 | 2.5 | 2.9 | 58.5 |
120 | 3.4 | 1.6 | 2.5 | 3.0 | 62.0 |
150 | 3.4 | 1.6 | 2.5 | 3.1 | 65.5 |
185 | 3.4 | 1.7 | 2.5 | 3.2 | 69.5 |
240 | 3.4 | 1.8 | 3.15 | 3.4 | 76.0 |
300 | 3.4 | 1.9 | 3.15 | 3.6 | 81.5 |
400 | 3.4 | 2.0 | 3.15 | 3.8 | 89.0 |
Cross sectional area mm² | Current Ratings | Short Circuit Ratings | |||
Laid in ground Amps | Drawn into twin wall ducts Amps | Laid in air Amps | One second short circuit rating of conductor kA | One second short circuit rating of armour kA | |
70 | 195 | 160 | 215 | 6.6 | 10.8 |
95 | 235 | 190 | 265 | 9.0 | 11.6 |
120 | 265 | 220 | 300 | 11.3 | 12.5 |
150 | 300 | 245 | 340 | 14.2 | 13.1 |
185 | 335 | 280 | 390 | 17.5 | 14.0 |
240 | 390 | 325 | 460 | 22.7 | 18.3 |
300 | 435 | 360 | 525 | 28.3 | 19.7 |
400 | 500 | 415 | 610 | 37.8 | 21.7 |